Eaton Power Xpert C445 User Manual page 267

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Input Instance 117 (0x75): Full Monitoring with Basic Analog and Digital Inputs, continued
Length = 46 Bytes
Byte
Size
Offset
(bytes)
Name
32
4
Trip Reason
36
4
Warning Reason
40
2
Thermal Pile
Percentage
42
2
Digital Inputs
44
2
Analog Inputs
Description
STATUS_TRIPPED_BITS, continued
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection
STATUS_WARNING_BITS
Warning/Alarm Indications
0x0000 0001 - under voltage
0x0000 0002 - over voltage
0x0000 0004 - Reserved
0x0000 0008 - ground current warning
0x0000 0010 - current phase loss
0x0000 0020 - current unbalance
0x0000 0040 - instantaneous over current
0x0000 0080 - jam
0x0000 0100 - PF deviation
0x0000 0200 - voltage phase loss
0x0000 0400 - voltage unbalance
0x0000 0800 - freq deviation fast
0x0000 1000 - freq deviation slow
0x0000 2000 - under current
0x0000 4000 - high power
0x0000 8000 - low power
0x0001 0000 - Reserved
0x0002 0000 - exceeds starts limit
0x0004 0000 - overload
0x0008 0000 - stall
0x0010 0000 - phase rotation mismatch
0x0020 0000 - PTC
0x0040 0000 - under voltage restart
0x0080 0000 - peak demand
0x0100 0000 - HRGF pulse detection
OVLD_THERMAL_MEM_PERCENT:
Thermal Capacity
0% Cold Motor
100% Will Cause an Overload Trip (%)
Bits 0-7 = Inputs for the first digital input card
Bits 8-15 = Inputs for the second digital input card
1 Input word of data for an analog output card status
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Appendix C—Optional Communication Cards
253

Advertisement

Table of Contents
loading

Table of Contents