Table 128. C445 Modbus Register Map, continued
Register
Name
6006
User Interface USB Modbus
Timeout
6007
Modbus TCP Timeout
6008
Webservices
Communication Timeout
6010
Present IP Address
6012
Present Subnet Mask
6014
Present Gateway
6016
Stored IP Address
6018
Stored Subnet Mask
6020
Stored Gateway
6022
Ethernet Port 1 Speed
Select
Attribute
UINT16 RW NV
Default: 0
Units: ms
Backup Mem
UINT16 RW NV
Default: 2000
Units: ms
Config CRC
Admin Lock
USB Lock
UINT16 RW NV
Default: 0
Units: ms
Config CRC
Admin Lock
USB Lock
UINT8 RO
Array size: 4
UINT8 RO
Array size: 4
UINT8 RO
Array size: 4
UINT8 RW NV
Array size: 4
Default: 0xFE, 0x01, 0xA8,
0xC0
Config CRC
Admin Lock
USB Lock
UINT8 RW NV
Array size: 4
Default: 0x00, 0xFF, 0xFF,
0xFF
Config CRC
Admin Lock
USB Lock
UINT8 RW NV
Array size: 4
Default: 0x01, 0x01, 0xA8,
0xC0
Config CRC
Admin Lock
USB Lock
UINT16 RW NV
Default: 100
Enum
Units: Mbs
Config CRC
Admin Lock
USB Lock
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Appendix D—Modbus Register Map
Description
The time before Modbus communications are considered lost. Every valid
message received will reset this timer. The timeout is in milliseconds.
When this timer expires, communication loss behavior will be triggered.
A value of zero (0) will disable the communication timeout.
The time before Modbus TCP communications are considered lost.
Every valid message received will reset this timer. The timeout is in
milliseconds. When this timer expires, communication loss behavior will
be triggered. A value of zero (0) will disable the communication timeout.
The time before HTTP REST communications are considered lost. Every
valid poll assembly message received will reset this timer. The timeout is
in milliseconds. When this timer expires, communication loss behavior
will be triggered. A value of zero (0) will disable the communication
timeout.
The Active IP Address being used on the Network.
Array of 2 registers
The Active Subnet Mask IP Address being used on the Network.
Array of 2 registers
The Active Default Gateway IP Address being used on the Network.
Array of 2 registers
The IP address used in the NV address select configuration. The DIP
switch settings on the Base Control Module determine if a static IP
address of 192.168.1.x, where x= the value on the DIP switch settings is
used, or if DHCP is used or if the IP address stored at this parameter is
used. To use this IP address, enter an IP address for this parameter,
power down the C445, set the DIP switches for the NVMEM selection and
when the unit is powered again, the C445 Ethernet module will be using
this IP address.
Array of 2 registers
The IP subnet mask used in the NV address select configuration. If the
DIP switches on the Base Control Module are set for NVMEM, this IP
subnet mask will take effect following a power cycle.
Array of 2 registers
The IP default gateway used in the NV address select configuration.
Array of 2 registers
Select the Ethernet link speed. Only used when Auto-Negotiate is
disabled.
Value
10
10 Mbps
100
100 Mbps
Description