Chapter 9—C445 Logic Engine and Expansion I/O
Flow Control Example
In this example, the TripClass System parameter is set to 10 during the first scan of the
program before allowing external digital inputs X0 and X1 to start the motor. The JMP will
always jump to LBL_1, skipping the segment of the program that sets the trip class except
during the first scan when its input condition will be FALSE.
166
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com