Ground Fault
The Residual Ground Fault protection monitors the ground
current of the motor and will trip the motor if the ground
current exceeds the set threshold. The Ground Fault
protection is always active.

Table 40. Ground Fault

Fault
Code
Protection
Action
4
Ground Fault
Fault Trip
(earth)
Fault Warning
Fault Trip Delay
Use Fault Trip
Inhibit
Fault Trip Inhibit -
Run
Note
1
ABC wiring recommended.
Note: Refer to Chapter 10 for information concerning the
External Ground Fault module and the Pulse Detect
Ground Fault feature.

Supply Protection

The C445 monitors the supply voltage to the motor for the
faults described below. These protections are only available
if the C445 Measurement Module has the voltage option.
Users can easily customize protection settings in the
protection menu of the Monitoring User Interface or of
Power Xpert inControl.
To enable/disable individual trip and warning protections,
navigate to Protections R General R Trip Enable / Warning
Enable.
Fault Action
Modbus
Units
Frame
1060
amps
C445MA2P4...
C445MA005...
C445MA032...
C445MA045...
C445MB072...
C445MC090...
C445MC136...
C445M...EXT
1061
1064
1065
%
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Min.
Max.
Default
0.12
2.4
1
0.25
5
3
1
9.6
3
1
1
13.5
3
1
3
1
21.6
3
3
27
3
34
40.8
34
30% of CT
50% of CT
50% of CT
Primary
Primary
Primary
At powerup
Disable
Enable
Disable
25
100
50
To customize protection levels and delays for each protection
feature, navigate to the category of that protection in
Protections R Current / Voltage / Power / Frequency /
Ground Fault
When the Supply fault is enabled in Trip mode, the C445 will
trip if a Voltage fault is detected when the motor is running.
In this mode, a Start will be inhibited if the fault condition is
present. Starts will be allowed as soon as the fault condition
is cleared.
Users may also optionally inhibit starting based on presence
of a voltage fault. To inhibit starting based on voltage faults,
enable "Inhibit Start on Voltage Fault" in the Protections R
General menu.
Chapter 6—Motor Protection
Delay (Seconds)
Min.
Max.
Default Modbus
1
60
5
1063
1
60
5
1063
1
60
5
1063
1
60
5
1063
1
60
5
1063
1
60
5
1063
1
60
5
1063
1
60
5
1063
2
1079
0
5
0
1062
0
0
0
133

Advertisement

Table of Contents
loading

Table of Contents