Appendix D—Modbus Register Map
Table 128. C445 Modbus Register Map, continued
Register
Name
346
Run Time Lifetime
348
Number Starts Lifetime
350
Operating Seconds Lifetime
352
Run Time Resettable
354
Number Starts Resettable
356
Operating Seconds
Resettable
358
Contactor Operations Last
Hour
359
Last Run Time
361
Last Starting Time
362
I Average % of FLA
363
Current Demand Value
365
Demand (Resettable)
367
Peak Demand Time Stamp
314
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Attribute
Description
UINT32 RO
Total motor run time in seconds
Units: seconds
Backup Mem
UINT32 RO
Total Number of Motor Starts in lifetime, not resettable.
Manufacturing Lock
Backup Mem
UINT32 RO
Total number of Seconds the motor has been running. Not resettable.
Units: seconds
Backup Mem
UINT32 RW NV
Total motor run time in seconds (Resettable). Resettable values can be
zero-ed out by the user at any time.
Default: 0
Units: seconds
Admin Lock
USB Lock
Backup Mem
UINT32 RW NV
Total number of motor starts (Resettable).
Default: 0
Admin Lock
USB Lock
Backup Mem
UINT32 RW NV
Total number of Seconds the motor has been running since this value
was last reset. This value is resettable.
Default: 0
Units: seconds
Backup Mem
UINT16 RO
Number of Contactor Operations During the Last Hour
Backup Mem
UINT32 RO
Duration in Seconds of the Last Start-to-Stop Motor Run Time
Default: 0
Units: seconds
UINT16 RO
The amount of time the motor took to get up to speed on the last start.
Default: 0
Units: seconds
UINT16 RO
Monitored Average Motor Current as Percentage of FLA (Nominal
Current)
Units: %
UINT32 RO
Latest estimate of the Demand measured over the demand window
duration.
Units: W
UINT32 RW NV
Peak Demand, User Resettable. The peak demand is updated if the
new demand calculated over the demand window is greater than the
Default: 0
previous peak.
Range: 0 to 0
Units: W
Admin Lock
USB Lock
Backup Mem
UINT32 RO
Peak Demand Time Stamped (in Unix time)
Default: 0
Units: seconds
Admin Lock
USB Lock
Backup Mem