Table 128. C445 Modbus Register Map, continued
Register
Name
1000
Trip Enable
1002
Warning Enable
Attribute
BYTE RW NV
Array size: 4
Default: 0x38, 0x00, 0x04,
0x00
Bitfield
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
BYTE RW NV
Array size: 4
Default: 0
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Appendix D—Modbus Register Map
Description
Enable protections by selecting the box next to each protection to place a
check mark in it. Each protection selected will enable those protections
that the C445 will trip on, continued.
Bit
Description
16
Reserved
17
Starts limit exceeded
18
Overload
19
Stall
20
Phase rotation mismatch
21
PTC
22
Under voltage restart
23
Peak demand
24
HRGF pulse detection
Any Warnings needed for an application may be enabled by selecting the
box next to each to place a check mark in it. Each protection selected will
enable those protections the C445 will provide a warning for when that
condition occurs.
Bit
Description
0
Under voltage
1
Over voltage
2
Reserved
3
Ground current warning
4
Current phase loss
5
Current unbalance
6
Instantaneous over current
7
Jam
8
Power factor deviation
9
Voltage phase loss
10
Voltage unbalance
11
Frequency deviation fast
12
Frequency deviation slow
13
Under current
14
High power
15
Low power
16
Reserved
17
Starts limit exceeded
18
Overload
19
Stall
20
Phase rotation mismatch
21
PTC
22
Under voltage restart
23
Peak demand
24
HRGF pulse detection
Coil
16001
16002
16003
16004
16005
16006
16007
16008
16009
Coil
16017
16018
16019
16020
16021
16022
16023
16024
16025
16026
16027
16028
16029
16030
16031
16032
16033
16034
16035
16036
16037
16038
16039
16040
16041
353