Accessories; Table 1. Suggested Current Transformers; Table 2. Catalog Numbers: C445Xc; Table 3. Catalog Numbers: D77E - Eaton Power Xpert C445 User Manual

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Chapter 1—Power Xpert C445 Overview

Accessories

Current Transformer
C445 measurement modules are designed to be used in
applications up to 136 A. For applications beyond 136 A,
external CTs with a 5 A output may be used.
CT Kits do not include Measurement Modules.

Table 1. Suggested Current Transformers

CT Range (A)
Description
17–300
300:5 Single-Phase CT, 1.25 inch dia hole, UL & CSA
ANSI/IEEE C57.13, 50–400 Hz, 600 Vac, 10 kV, relay
class C50, accuracy 0.3% B0.1
75–600
600:5 Single-Phase CT, 2.00 inch dia hole, UL & CSA
ANSI/IEEE C57.13, 50–400 Hz, 600 Vac, 10 kV, relay
class C50, accuracy 0.3% B0.1
100–800
800:5 Single-Phase CT, 2.50 inch dia hole, UL & CSA
ANSI/IEEE C57.13, 50–400 Hz, 600 Vac, 10 kV, relay
class C50, accuracy 0.3% B0.1
Note
1
Catalog numbers are for one CT. Order 3 for a three-phase system. Customer supplied CTs may be also be used. See section on using C445 with external CTs.
Communication and Option Modules
Table 2. Catalog Numbers: C445XC... Optional Communication Cards and
C445XO... Modules
Description
EtherNet/IP and Modbus TCP card with 2-port switch
PROFIBUS DPV1 and DPV0 card
Real-Time Clock and Memory Backup Module
Cables, Wiring Harnesses and Spare Parts
D77E connection cables are required to connect the Base
Control Module to the Measurement Module and to the user
interface. Use the appropriate lengths for each connection.
Table 3. Catalog Numbers: D77E... RJ-12 Cables
Description
Connection cable (Base Control Module to Measurement Module or user interface), 13 cm length
Connection cable (Base Control Module to Measurement Module or user interface), 25 cm length
Connection cable (Base Control Module to Measurement Module or user interface), 100 cm length
Connection cable (Base Control Module to Measurement Module or user interface), 200 cm length
Connection cable (Base Control Module to Measurement Module or user interface), 300 cm length
User interface wiring harnesses are required to utilize the
digital inputs on the Control Family of User Interfaces.
Use one wiring harness per user interface to connect to
these inputs.
4
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
1
Terminal Size
(2) 8–32 brass terminals,
comes with mounting
bracket kit
(2) 8–32 brass terminals,
comes with mounting
bracket kit
(2) 8–32 brass terminals,
comes with mounting
bracket kit
Catalog Number
C445XC-E
C445XC-P
C445XO-RTC
Measurement Module
Catalog Number
C445MA-005_
XCT300-5
C445MA-005_
XCT600-5
C445MA-005_
XCT800-5
Catalog Number
D77E-QPIP13
D77E-QPIP25
D77E-QPIP100
D77E-QPIP200
D77E-QPIP300

Advertisement

Table of Contents
loading

Table of Contents