Eaton Power Xpert C445 User Manual page 280

Global motor management relay
Hide thumbs Also See for Power Xpert C445:
Table of Contents

Advertisement

Appendix C—Optional Communication Cards
Table 98. Control Supervisor Object—Class 0x29 (41), continued
Instance Attributes
Sr. No.
ID
Access Rule
17
106 (0x6A) Get
18
107 (0x6B) Get
266
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Data Type
Description
Array of 4 Bytes Tripped Status
Bits
Array of 4 Bytes Warning Status
Bits
Bit 0: Undervoltage
Bit 1: Overvoltage
Bit 2: Reserved
Bit 3: Ground current fault
Bit 4: Current phase loss
Bit 5: Current unbalance
Bit 6: Instantaneous over current
Bit 7: Jam
Bit 8: PF deviation
Bit 9: Voltage phase loss
Bit 10: voltage unbalance
Bit 11: Freq deviation fast
Bit 12: Freq deviation slow
Bit 13: Under current
Bit 14: High power
Bit 15: Low power
Bit 16: Reserved
Bit 17: Exceeds starts limit
Bit 18: Overload
Bit 19: Stall
Bit 20: Phase rotation mismatch
Bit 21: PTC
Bit 22: Under voltage restart
Bit 23: Peak demand
Bit 24: HRGF Pulse Detection
Bit 0: Undervoltage
Bit 1: Overvoltage
Bit 2: Reserved
Bit 3: Ground current warning
Bit 4: Current phase loss
Bit 5: Current unbalance
Bit 6: Instantaneous over current
Bit 7: Jam
Bit 8: PF deviation
Bit 9: Voltage phase loss
Bit 10: Voltage unbalance
Bit 11: Freq deviation fast
Bit 12: Freq deviation slow
Bit 13: Under current
Bit 14: High power
Bit 15: Low power
Bit 16: Reserved
Bit 17: Exceeds starts limit
Bit 18: Overload
Bit 19: Stall
Bit 20: Phase rotation mismatch
Bit 21: PTC
Bit 22: Under voltage restart
Bit 23: Peak demand
Bit 24: HRGF Pulse Detection