Appendix D—Modbus Register Map
Table 128. C445 Modbus Register Map, continued
Register
Name
1030
Undervoltage Start Delay
1031
Undervoltage Trip Delay
1032
Voltage Loss Restart Loss
Level
1033
Voltage Loss Restart Return
Level
1034
Voltage Loss Restart Auto
Time
1035
Voltage Loss Restart Short
Delay
358
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
Attribute
Description
Undervoltage Start Delay is a delay to prevent this protection, if enabled,
UINT16 RW NV
from tripping the motor at start up until this time expires. If the
Default: 20
Undervoltage condition is still present after this time delay, then a trip
Range: 0 to 60
would occur following the Undervoltage Trip Delay Time.
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Undervoltage Trip Delay is the time delay following the trip level being
exceeded until a trip occurs.
Default: 20
Range: 1 to 60
Units: seconds
Config CRC
Admin Lock
USB Lock
Backup Mem
UINT8 RW NV
Voltage Loss Restart Loss Level is the level of voltage that C445 will
consider a voltage loss to start the time intervals for Voltage Loss Restart
Default: 70
Action.
Range: 65 to 90
Units: %
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Voltage Loss Restart Return Level is the voltage level that line voltage
UINT8 RW NV
must return to for C445 to re-start motors. If the level returns to this point
Default: 90
or above within the time intervals specified by the user (VLR Short Time
Range: 80 to 100
and VLR Long Time), a restart sequence will be initiated according to user
Units: %
settable delays (VLR Short Delay and VLR Long Delay).
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT16 RW NV
Voltage Loss Restart Time Interval for The Auto Time Period. C445 will
hold its output relay shut for this time period after voltage loss to
Default: 200
automatically pull the contactor back in as soon as voltage returns. If
Range: 100 to 400
control power is lost, C445 can remain powered for approximately 200ms
Units: ms
at 70% control power.
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
UINT32 RW NV
Voltage Loss Restart Short Delay. If voltage returns to the user specified
level within the short time period C445 will send a command to re-start
Default: 1000
the motor after the Short Time Delay.
Range: 100 to 500000
Units: ms
Config CRC
Admin Lock
USB Lock
Backup Mem