Fitting the Devices
3.1 Flush-Mounting Devices
Produce the holes as shown in the drilling plan.
²
Fitting Devices
Detach the top and bottom plastic screw covers of each on-site operation panel.
²
Insert the device in the installation opening. Make sure that the fastening screws of the on-site operation
²
panels also protrude exactly into the openings (6-mm diameter (0.24-in diameter)).
With the M4 oval head cap screws, bolt down the device at the top and bottom at all 4 bolting points of
²
each module.
Check for secure attachment.
²
Fit the top and bottom plastic screw covers again.
²
3.1.3

Activating the Battery

Removing the Protective Film
NOTE
i
i
The battery is covered with a protective film to protect it from mechanical damage and against premature
discharge.
The battery need not be removed from the battery compartment for activation.
Pull out the battery compartment.
²
Remove the protective film from the battery by simply pulling on the film tab.
²
Push the battery compartment back in again.
²

Grounding and Connecting Devices

3.1.4
Grounding the Devices
The SIPROTEC 5 devices are protection class I equipment must be connected with the system ground before
commissioning.
!
DANGER
Danger due to device being improperly grounded
Incomplete and careless grounding leads to death, severe injury, and considerable material damage!
The device must be situated in the operating area for at least 2 hours before you connect it to the
²
power supply for the first time. This method prevents condensation of water in the device.
If the device has been in storage for more than 2 years, connect it to an auxiliary voltage for 1 to 2
²
days. This will cause the electrolytic capacitors to form on the printed circuit board assemblies again.
Ground each module with solid low-impedance system grounding (cross-section ≥ 4.0 mm
²
grounding area ≥ M4).
Connecting Devices
Connect all cables and leads. Use the connection diagrams in the Hardware and Device manuals.
²
Tighten the terminal screws to the prescribed torques.