Advertisement

Operation in the Operating State
8.5 Edit Measured and Metered Values
Measured / Metered
Values
Energy values
Statistical values
User-defined measured
values

Reading Measured Values and Metered Values

8.5.2
You can read measured and metered values on the device display or with DIGSI 5. You find these values in the
respective function groups such as the Line function group. Take note that the scope of measured values is
determined by the type and number of assigned measuring points. If only one measuring point, for example,
3-phase current, is assigned to the function group, then all measured values linked to the voltage (voltage,
power, energy) are omitted. These measured values are hidden automatically.
It is then explained later by example how you reach the individual measured values.
a) Reading Measured Values on the Device
Main menu → Measured values
Line 1 (function group)
Operational Measured Values
Displaying available measured values (see
Fundamental component/symmetrical components
Displaying available measured values (see
Function measured values (protection-specific measured values)
Displaying available measured values (see
Minimum/maximum/average values
Displaying available measured values (see
Energy
Displaying available metered values (see
User-defined measured values
Displaying metered values (see
Displaying measured values
142
Description
These metered values are determined for active and reactive energy. Restore
time, restore interval and counting mode are adjustable. Restoration can be
initiated via a binary input.
The following metered values are available:
Active energy Wp+ (export), Wp- (import)
Reactive energy Wq+ (export), Wq- (import)
The following statistical values are formed:
Number of initiated switching operations of the circuit breaker (opera-
tion counter); the contactor trips and switch actuations by the control
are counted.
Number of initiated switching operations of the circuit breaker, sepa-
rated by circuit-breaker pole
Sum of total primary breaking currents
Sum of the primary breaking currents, separately for each breaker pole
These metered values can be determined for any metered amounts received
via a binary input.
The unit and significance of a pulse, restore time, restore interval, and
meter mode can be set.
Restoration can be initiated via a binary input
Table
Table
8-7)
Table
8-7)
Table
8-7)
Table
8-7)
Table
8-7)
8-7)