Commissioning
7.2 Test Suite Integrated in the Device
[scgerinf-100413-01.tif, 1, en_US]
Figure 7-8
Device information:
General information about the device such as device name, product code and serial number is indicated
here. If the device uses Ethernet, you can select at this point the IP address of the device through which
DIGSI 5 communicates with the device (port J, this setting only available in offline mode). You can
furthermore set the device language here, as well as the operating modes (process mode, commissioning
mode).
Resource consumption:
The first area shows you the state of the device load offline. If it is green, the parameterization can be
loaded into the device and real-time behavior ensured. If the lamp is red, functionality must be reduced.
The number of used function points is shown to you in the second area. If the allowed number is
exceeded, replacements must be bought for device-related function points. To reorder, use the configu-
rator and follow the menu instructions there.
In the 3rd area you are shown the capacity utilization of the operational diagram (Continuous function
chart, or CFC in short).
Log
Device diagnosis log:
Monitoring indications are entered in this buffer. If, for example, a device fault is present, the
required information is entered in plain text. Every result is time-stamped. Plain text means that you
receive the necessary information about, say, erroneous modules and the type of error. At the same
time, an operation recommendation such as replacement of the expansion module is given.
Safety indications:
In this buffer logs, entries are time-stamped when access was carried out on the device using
DIGSI 5. Rejected access, for example, if you entered the password incorrectly 3 times, is registered.
You cannot delete this buffer. This buffer is organized as a ring buffer. Selected indications can be
transmitted to a systems control and can be archived there. This guarantees a long-term buffer for
accessing the device as it is required in cyber-security recommendations such as NERC-CIP (see
chapter10.1 Security
Time information:
In this setting sheet you can open diagnoses for the first and second clock and query their synchroniza-
tion status. In addition, it gives information about the internal device time. This can also be set via this
menu for test purposes. If a high-precision second pulse is available, its status is also shown here
8.7.3 Setting Time Keeping Parameters
92
Device-Information Worksheet
Design).
.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016