Siemens SIPROTEC 5 Operation Manual page 187

V7.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Diagnostic Log
Maximum number of load breaking switches exceeded
Maximum number of bays exceeded
Auxiliary-power supply failure:
Check the external power supply.
Either 1 busbar disconnector or 1 line disconnector allowed
Maximum number of Busbar DC & Transferbus DC exceeded
Undefined bay type
Undefined disconnector type
At least one Feeder is necessary
Failure of device configuration:
Check the logs for reasons and upload valid configuration into device.
The voltage measured values indicate a failure.
There is no CFC logic available or a negative ID of measuring point is selected for Function block Voltage
measuring-point selection (1ph).
The voltage measured values indicate a failure.
There is no CFC logic available or a negative ID of measuring point is selected for Function block Voltage
measuring-point selection (3ph).
A non-existing voltage measuring point ID is selected for Function block Voltage measuring-point selection
(1ph). Please check your CFC logic.
A non-existing voltage measuring point ID is selected for Function block Voltage measuring-point selection
(3ph). Please check your CFC logic.
Failure in data structure:
Contact the repair service.
Firmware-version failure:
Update the device firmware.
If the failure remains, contact the repair service.
Bus link failure:
Check the connection of the modules.
Update the device firmware.
If the failure remains, contact the repair service.
The IEC 61850 protocol could not be started up successfully. Too many protection functions might be config-
ured leading to a memory leakage problem for protocol data. Protocol health set to alarm. Reduce the
amount of configured protection functions.
Error instantiating a GOOSE control block for subscription. Too many protection functions might be config-
ured leading to a memory leakage problem for protocol data. Protocol health set to alarm. Reduce the
amount of configured protection functions.
Internal power supply failure:
Contact the repair service.
Module update failure:
Check the module interconnection and carry out the update again.
If the failure remains, contact the repair service.
Hardware failure:
Contact the repair service.
A failure could not be solved automatically:
Check the previous entries of device-diagnosis log.
If the failure remains, contact the repair service.
Signature failure:
Contact the repair service.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
Maintenance, On-the-Spot Assistance and Test
9.2 Error Search and Correction
187