[dweinbpr-070211-01.tif, 1, en_US]
Figure 3-2
Refer to
Table 3-2

Fitting Devices

3.1.2
Preparations
NOTE
i
i
The installation depth for 1 device is at least 275 mm (11.83 in). This dimension includes the necessary
bending radius for the various connectors of the plug-in modules.
The M4 holes are the holes for the fastening screws of the device. The Ø 6 holes are the openings for the
fastening screws of the on-site operation panels on the device.
NOTE
i
i
Use a PZ2-size Phillips screwdriver.
For each module, you need 4 fastening screws with a shank diameter of 4 mm (0.16 in).
!
WARNING
Danger due to device being improperly screw-fastened
Incomplete and careless screw-fastening can lead to death, severe injury, and considerable material
damage.
Ensure that screw-fastening is complete at all intended bolting points. Tighten the screws to a torque
²
of 1.2 Nm.
If no assembly opening is prepared, then cut out the required assembly opening.
²
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016
Flush-Mounting Devices, Dimensions from the Side and Front Views
for the variable dimension a.