Operation in the Operating State
8.8 Control System on Site
[scstatus-280513-01.tif, 1, en_US]
Figure 8-67
[scstatu2-280513-01.tif, 1, en_US]
Figure 8-68
NOTE
i
i
For safety reasons, manual updating is possible only directly through the on-site operation panel of the
device and not through DIGSI 5.
NOTE
i
i
Setting acquisition blocking and the subsequent manual updating are also possible via the IEC 61850
system interface.
Acquisition blocking can also be set via a binary input. This way, acquisition blocking can be set for an indi-
vidual or several switching devices in a feeder simultaneously with an external toggle switch in order to
disable the feeder. For this purpose, every switching device in the Switch function block (circuit breaker or
disconnector switch) has the input signal >Acquisition blocking. This signal can also be set from the
CFC.
172
Activate Manual Updating
Selecting Position
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016