Operation in the Operating State
8.6 Fault Recording
[scusrrec-080413-01.tif, 1, en_US]
Figure 8-41
The start criterion can also be entered via an external start signal of the Fault recording function
(>External start). With this you can, for example, initiate recording of a fault record using an
external protection device without internal fault recording in case of pickup.
A test fault record can also be initiated manually via the on-site operation panel of the device (for
example, via function key) or via DIGSI 5. For this, a freely configurable start signal (>Manual Start) is
available.
[scmnstrt-080413-01.tif, 1, en_US]
Figure 8-42
152
User-Defined Configuration of the Start Criterion for Fault Recording
Manual Start via DIGSI 5
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-7, Edition 06.2016