PWR (green)
Lit
 Checking Errors in the EtherCAT Master Function Module and EtherNet/IP
Function Module
For the EtherCAT Master Function Module and EtherNet/IP Function Module, use the EtherCAT and
EtherNet/IP NET ERR indicators to determine whether an error that affects process data communi-
cations has occurred and whether a minor fault level error or higher-level error has occurred. The
indicators let you check the status given in the following table.
Indicators
EtherCAT
NET ERR
EtherNet/IP
NET ERR
Checking with the Troubleshooting Function of Sysmac Studio
When an error occurs, you can connect the Sysmac Studio online to the Controller to check current
Controller errors and the log of past Controller errors.
 Current Errors
Open the Sysmac Studio's Controller Error Tab Page to check the current error's level, source,
source details, event name, event code, details, attached information 1 to 4, actions, and correc-
tions. Errors are not displayed for observations.
 Log of Past Errors
Open the Sysmac Studio's Controller Event Log Tab Page to check the times, levels, sources,
source details, event names, event codes, details, attached information 1 to 4, actions, and correc-
tions for previous errors.
Error logs from CJ-series Special Units are displayed on the Controller Event Log Tab Page.
Detailed information is not displayed. To check detailed information, use the event codes that are
displayed and refer to the error codes that are given in the manual for the relevant Unit. The relation-
ship between error codes and event codes is described in Details on Controller Events (Errors and
Information) under 1-3-1 Types of Non-fatal Errors.
Refer to the NJ-Series Sysmac Studio Version 1 Operation Manual (Cat. No. W504) for details on
troubleshooting with the Sysmac Studio.
Checking with the Troubleshooter of an NS-series PT
When an error occurs, if you can connect communications between an NS-series PT and the Control-
ler, you can check current Controller errors and the log of past Controller errors.
To perform troubleshooting from an NS-series PT, connect the PT to the built-in EtherNet/IP port on the
CPU Unit.
NJ-series Troubleshooting Manual (W503)
Indicators
RUN (green)
ERROR (red)
Lit
Indicated status
EtherCAT Master Function Module Status
• Lit: Errors for which normal status cannot be recovered through user actions (i.e., errors
for which you must replace the CPU Unit or contact your OMRON representative).
• Flashing: Errors for which normal status can be recovered through user actions.
• Not lit: An error that affects process data communications has not occurred.
EtherNet/IP Function Module Status
• Lit: Errors for which normal status cannot be recovered through user actions (i.e., errors
for which you must replace the CPU Unit or contact your OMRON representative).
• Flashing: Errors for which normal status can be recovered through user actions.
• No lit: There are no minor fault level or higher-level errors.
1 Overview of Errors
Not lit
Event level
Observation
1-13