Event code
Event name
04AC0000 hex
Overcurrent
04AD0000 hex IPM Error
04AE0000 hex
Regenera-
tion Tr Error
04AF0000 hex
Encoder
Phase-Z
Error
04B00000 hex
Encoder CTS
Signal Error
04B10000 hex
Node
Address Set-
ting Error
04B20000 hex
Other Errors
08080000 hex
Encoder
Communica-
tions Discon-
nection Error
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The current flowing
• A short-circuit, line-to-ground
through the con-
fault, contact failure, or insula-
verter exceeded the
tion failure occurred on the U, V,
specified value.
or W motor line.
• The Servo Drive failed.
• The relay for the dynamic brake
has been welded due to fre-
quent Servo ON/OFF opera-
tions.
• Motor windings are burned out.
• The Servomotor is not suitable
for the Servo Drive.
• The command input timing is
the same as or earlier than the
Servo ON timing.
The current flowing
• A short-circuit, line-to-ground
through the con-
fault, contact failure, or insula-
verter exceeded the
tion failure occurred on the U, V,
specified value.
or W motor line.
• The Servo Drive failed.
• The relay for the dynamic brake
has been welded due to fre-
quent Servo ON/OFF opera-
tions.
• Motor windings are burned out.
• The Servomotor is not suitable
for the Servo Drive.
• The pulse input timing is the
same as or earlier than the
Servo ON timing.
The Servo Drive
• The Servo Drive regeneration
regeneration drive
drive Tr is faulty.
Tr is faulty.
A missing serial
• The encoder is faulty.
incremental
encoder phase-Z
pulse was detected.
A missing serial
• The encoder is faulty.
incremental
encoder CTS signal
logic error was
detected.
The node address
• The Servo Drive failed.
that was read from
the rotary switches
was not between 00
and 99.
The Servo Drive
• The control circuit malfunc-
malfunctioned, or
tioned temporarily due to
an error occurred in
excess noise.
the Servo Drive.
• The Servo Drive's self-diagno-
sis function detected an error in
the Servo Drive.
A disconnection
• The encoder is not wired cor-
was detected
rectly.
because communi-
cations between the
encoder and the
Servo Drive were
stopped more fre-
quently than the
specified value.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
Cylinder-type
Motor Manual
(Cat. No. I576)
and Linear
Motor Manual
(Cat. No. I577)
S
Same as
above.
S
Same as
above.
S
Cylinder-type
Motor Manual
(Cat. No. I576)
S
Same as
above.
S
Cylinder-type
Motor Manual
(Cat. No. I576)
and Linear
Motor Manual
(Cat. No. I577)
Linear Motor
S
Manual (Cat.
No. I577)
S
Cylinder-type
Motor Manual
(Cat. No. I576)
Reference
3
3-77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nj501-1500Nj501-1400Nj501-1300Nj301-1200Nj301-1100

Table of Contents