Omron NJ Series Troubleshooting Manual page 35

Machine automation controller sysmac
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Operation in the Function Module Where an Error Event Occurred
Event level
Function
module
PLC Function
Module
Motion Control
Function Module
EtherCAT Master
Function Module
EtherNet/IP Func-
tion Module
I/O Operation for Major Fault Level Controller Errors
The following table gives the operation of the CPU Unit and the I/O devices for the following errors.
• Unsupported Unit Detected
• I/O Bus Check Error
• End Cover Missing
• Incorrect Unit/Expansion Rack Connection
• Duplicate Unit Number
• Too Many I/O Points
• I/O Setting Check Error
Unit
*1
EtherCAT slave
Servo Drives assigned to an axis
NJ-series Troubleshooting Manual (W503)
Major fault level
Partial fault level
User program execution
---
stops.
All axes stop. (The stop
All axes stop. (The
method depends on the
stop method depends
error.)
on the error.)
I/O refreshing for EtherCAT
EtherCAT communi-
communications stops. (The
cations stop. (The
slaves operate according to
slaves operate
the settings in the slaves.)
according to the set-
tings in the slaves.)
Part of the EtherNet/IP
EtherNet/IP commu-
communications stop.
nications stop. (A
(Online connections to the
software connection
Sysmac Studio and commu-
from the Sysmac Stu-
nications connections with
dio or an NS-series
NS-series PTs are possible.
PT is not possible.)
(Output (produce) tags in
the tag data links operate
according to the tag set set-
tings.)
CPU Unit operation
The slave is placed in the Safe-
Operational state.
Updating the command values is
stopped.
1 Overview of Errors
Minor fault level
Observation
Operation continues.
• The affected
• Axis operation
axes/axes group
continues.
stops. (The stop
• The motion con-
method depends on
trol instruction is
the settings.)
not executed (for
• The motion control
instructions not
instruction is not exe-
related to axis
cuted (for instructions
operation).
related to axis opera-
tion.)
I/O refreshing for Ether-
I/O refreshing for
CAT communications
EtherCAT commu-
stops or continues
nications contin-
according to the fail-soft
ues.
operation settings in the
master. (If I/O refreshing
stops, the slaves oper-
ate according to the set-
tings in the slaves.)
Part of the EtherNet/IP
EtherNet/IP com-
communications stop.
munications con-
(A software connection
tinue.
from the Sysmac Studio
or an NS-series PT is
possible if the communi-
cations connection is
not the cause of the
error.)
Unit or slave operation
Depends on the slave settings.
All axes stop immediately.
1
*2
1-9