Errors In The Ethernet/Ip Function Module - Omron NJ Series Troubleshooting Manual

Machine automation controller sysmac
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

3 Error Tables
3-1-4

Errors in the EtherNet/IP Function Module

Built-in EtherNet/IP Port on CPU Unit
Event code
Event name
04200000 hex
Communica-
tions Control-
ler Failure
14200000 hex
MAC
Address
Error
14220000 hex
EtherNet/IP
Processing
Error
34210000 hex
Basic Ether-
net Setting
Error
34220000 hex
TCP/IP Basic
Setting Error
(Local Port IP
Address)
84010000 hex
IP Address
Duplication
Error
84020000 hex
BOOTP
Server Con-
nection Error
14210000 hex
Identity Error
34200000 hex
Tag Data Link
Setting Error
34230000 hex
TCP/IP
Advanced
Setting Error
(IP Router
Table)
3-68
Meaning
Assumed cause
A hardware error
• Communications Controller
was detected in the
hardware error
communications
controller of the
built-in EtherNet/IP
port.
The MAC address
• Non-volatile memory failure
in non-volatile
memory was not
read correctly.
A fatal error was
• Hardware has failed.
detected in the Eth-
erNet/IP Function
Module.
An error was
• Setting error
detected in the
• Power was interrupted when a
Ethernet settings.
download was in progress for
the Ethernet basic settings.
• Memory error
An error was
• Setting error
detected in the IP
• Power was interrupted when a
address settings.
download was in progress for
the TCP/IP basic settings.
• Memory error
• The IP address acquired from
BOOTP server is illegal.
The same IP
• The IP address of the built-in
address is used
EtherNet/IP port is also used as
more than once.
the IP address of another node.
Connection with the
• Server setting error
BOOTP server
• Server is down.
failed.
• An error occurred in the com-
munications path.
The CIP identity
• Non-volatile memory failure
information in non-
volatile memory
was not read cor-
rectly.
An error was
• Power was interrupted when a
detected in the
download was in progress for
communications
the data link settings.
settings for tag data
• Memory error
links.
An error was
• Setting error
detected in the
• Power was interrupted when a
hosts in the IP
download was in progress for
router table.
the TCP/IP advanced settings.
• Memory error
• There is a mistake in the IP
router table settings or hosts
settings.
Level
Maj
Prt
Min
Obs Info
S
NJ-series
CPU Unit
Built-in Ether-
Net/IP Port
User's Manual
(Cat. No.
W506)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)
Reference

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nj501-1500Nj501-1400Nj501-1300Nj301-1200Nj301-1100

Table of Contents