Event code
Event name
34850000 hex
Mean Value
Processing
Setting Error
34860000 hex
Error in Set-
ting of Con-
version Mode
34870000 hex
Output Hold
Setting Error
34890000 hex
Conversion
Time/Resolu-
tion or Oper-
ation Mode
Setting Error
348A0000 hex
Output Signal
Range Set-
ting Error or
Error In Num-
ber of Out-
puts Used
Setting
38010000 hex
Scaling Data
Setting
Error/Ratio
Conversion
Use Setting
Error
38020000 hex
Ratio Set
Value Error
64780000 hex
Input Discon-
nection
Detected
64790000 hex
Output Set
Value Error
34810000 hex
Input Value
Exceeded
Adjustment
Range in
Adjustment
Mode
34820000 hex
Input Number
Specification
Error in
Adjustment
Mode
34880000 hex
Output Num-
ber Specifi-
cation Error
in Adjustment
Mode
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
There is a mistake
• There is a mistake in the setting
in the setting of the
of the number of samplings for
number of sam-
mean value processing.
plings for mean
value processing.
There is a mistake
• The specification of the Cyclic
is the Conversion
Conversion Mode or Direct
Mode setting.
Conversion Mode is not correct.
There is a mistake
• The setting for output status
in the output hold
when conversion stops is incor-
setting.
rect.
There is a mistake
• There is a mistake in the con-
in the conversion
version time/resolution or oper-
time/resolution or
ation mode setting.
operation mode set-
ting.
There is a mistake
• There is a mistake in the output
in the output signal
signal range setting or in the
range setting or in
number of outputs setting.
the number of out-
puts setting.
There is an error in
• The upper or lower limit data for
the scaling data
scaling is outside the setting
setting or ratio con-
range. Or, the maximum value
version use setting.
and minimum value are not 0
and they are the same.
• The I/O number for ratio con-
version is set to Not used in the
I/O specifications.
There is a mistake
• A value other than 16#0000 to
is the ratio setting
16#9999 (0.00 to 99.99) was
for ratio conversion.
specified for the ratio conver-
sion A constant for ratio conver-
sion.
• Input wiring is broken.
The input is discon-
nected.
• Input wiring disconnection
The output setting
• An output set value setting is
is out of range.
out of range.
In Adjustment
• In Adjustment Mode, the input
Mode, the input
value exceeded the range for
value exceeded the
which adjustment is possible,
range for which
so the offset and gain cannot
adjustment is possi-
be adjusted.
ble.
The input number
• The input number that was
specified in Adjust-
specified in Adjustment Mode is
ment Mode is not
not enabled.
enabled or the input
• The setting of the Adjustment
number is wrong.
Input Number (device variable
*_AdjCh) is incorrect, so adjust-
ment is not possible.
The output number
• The output number that was
specified in Adjust-
specified in Adjustment Mode is
ment Mode is not
not enabled.
enabled or the out-
• The setting of the Adjustment
put number is
Output Number (device variable
wrong.
*_AdjCh) is incorrect, so adjust-
ment is not possible.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
CJ-series
Analog I/O
Units Opera-
tion Manual for
NJ-series
CPU Unit (Cat.
No. W490)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
U
Same as
above.
S
U
Same as
above.
U
S
Same as
above.
U
S
Same as
above.
U
S
Same as
above.
Reference