3
Parameterisation
3.1.7

Fail safe and Idle parameters

Assigning the instance numbers for the relevant object:
The first word receives the lowest instance number
The second word receives the second lowest instance number
...
Overview
Module type
Digital output modules
Analogue output modules
Technology modules
Tab. 3.28
Fail safe mode and Idle mode objects
Object classes:
Fail safe mode: 113
Idle mode: 115
, 123
d
Instances: 1 ... 48
Attribute no.
Access
1
Get/Set
2
Get/Set
...
...
64
Get/Set
100
Get
101
Get
Tab. 3.29
34
Object
Description
112
Fail safe state digital outputs
113
Fail safe mode digital outputs
114
Idle state digital outputs
115
Idle mode digital outputs
120
Fail safe state analogue outputs
121
Fail safe mode analogue outputs
122
Idle state analogue outputs
123
Idle mode analogue outputs
128
Fail safe state inputs, technology modules
129
Fail safe mode inputs, technology modules
130
Idle state outputs, technology modules
131
Idle mode outputs, technology modules
, 121
, 129
d
d
d
, 131
d
d
Description
Duct 0
0 = Hold last state
1 = Fail safe/Idle state
Channel 1
0 = Hold last state
1 = Fail safe/Idle state
...
Duct 63
0 = Hold last state
1 = Fail safe/Idle state
Number of channels
All channels: values for Fail safe mode and Idle mode
Type
BOOL
BOOL
...
BOOL
BYTE
ARRAY
Festo – CPX-E-EP-EN – 2017-07 – English