Function
2.3

Addressing

2.3.1

Basic rules for addressing

The address assignment of the inputs does not depend on the address assignment of the outputs.
The numbering goes from left to right.
The bus module counts as a module with 0 inputs and 0 outputs when the status bits and the I/O diagnostic
interface are deactivated.
Activated status bits occupy 8 inputs.
An activated I/O diagnostic interface occupies 16 inputs and 16 outputs.
The inputs and outputs of different module types are assigned separately from each other.
The following sequence applies:
1. Bus module with status bits or I/O diagnostic interface (if activated via DIL switch)
2. Analogue modules
3. Technology modules
4. Digital modules
2.3.2

Addressing example

1 Bus module CPX-E-EP (with status bits)
Status bits activated
I/O diagnostic interface deactivated
2 Digital input module CPX-E-16DI
3 Digital output module CPX-E-8DO
4 Digital output module CPX-E-8DO
5 Analogue input module CPX-E-4AI-U-I
6 Analogue output module CPX-E-4AO-U-I
Fig. 2.3
The address assignment for the system CPX-E presented is shown in Tab. 2.5.
Module no. Module
0
Bus module CPX-E-EP (with status bits)
1
Digital input module CPX-E-16DI
2
Digital output module CPX-E-8DO
3
Digital output module CPX-E-8DO
4
Analogue input module CPX-E-4AI-U-I
5
Analogue output module CPX-E-4AO-U-I
Tab. 2.5
Festo – CPX-E-EP-EN – 2017-07 – English
Module no.:
0
1
1
2
Input address
I0 ... I7
I72 ... I87
I8 ... I71
2
3
4
5
3
4
5 6
Output address
O64 ... O71
O72 ... O79
O0 ... O63