Function
2.1.7

Control components

Rotary/DIL
Function
switches
The 3 rotary switches are used to set the 4th octet of the IP address (192.168.1.XXX).
Possible settings:
0 = Dynamic addressing via DHCP/BOOTP
1 ... 255 = Permissible address range
Valid values:
EtherNet/IP: 300 ... 555 (IP address = value – 300)
Modbus TCP: 600 ... 855 (IP address = value – 600)
Factory setting: 900
The diagnostic mode is set using the DIL switches è Tab. 2.2.
Tab. 2.1
In the case of invalid values, the IP parameters are reset to dynamic addressing (DHCP).
For switch settings 0 ... 255, the EtherNet/IP and Modbus TCP protocols can be used in parallel.
The rights to control the outputs are assigned to the protocol that sends outputs first.
DIL switches
DIL 1: OFF
DIL 2: OFF
DIL 1: OFF
DIL 2: ON
DIL 1: ON
DIL 2: OFF
DIL 1: ON
DIL 2: ON
1) Factory setting
Tab. 2.2
Changes to the rotary and DIL switches only take effect following a restart of the bus module.
Festo – CPX-E-EP-EN – 2017-07 – English
Function
1)
No diagnostics
Status bits activated
I/O diagnostic interface activated
Reserved
9