Parameterisation
Ethernet Link Object
Object class: 246
d
Instances: 3
General information and status information as well as advanced settings for the Ethernet interfaces.
Instance 1 corresponds to Ethernet port X1 and instance 2 corresponds to Ethernet port X2.
Attribute no.
Access
1
Get
2
Get
3
Get
4
Get
5
Get
Festo – CPX-E-EP-EN – 2017-07 – English
Description
Interface speed (in Mbps)
Interface flags
Bit 0
Link status
0 = Inactive link
1 = Active link
Bit 1
Half duplex/Full duplex
0 = Half duplex
1 = Full duplex
Bit 2 ... 4
Negotiation status:
0 = Autonegotiation in progress
1 = Autonegotiation and speed detection failed
2 = Autonegotiation failed but detected speed
3 = Successfully negotiated speed and duplex
4 = Autonegotiation not attempted
Bit 5
Manual setting requires reset
Bit 6
Local hardware fault
0 = No local hardware fault
1 = Local hardware fault detected
Physical address (MAC layer address)
Interface counters
In octets
In Ucast packets
In NUcast packets
In discards
In errors
In unknown protos
Out octets
Out Ucast packets
Out NUcast packets
Out discards
Out errors
Media counters
Alignment errors
FCS errors
Single collisions
Multiple collisions
SQE test errors
Deferred transmissions
Late collisions
Excessive collisions
MAC transmit errors
Carrier sense errors
Frame too long
MAC receive errors
Type
UDINT
DWORD
ARRAY of UINT [6]
STRUCT of UDINT
STRUCT of UDINT