Objects For System Data And Diagnostics - Festo CPX-E-EP Manual

System cpx-e, bus module, protocol, ethernet/ip, modbus tcp, industrial ethernet 2-port
Table of Contents

Advertisement

3
Parameterisation
3.1.5

Objects for system data and diagnostics

Identity Object
Object class: 1
d
Instances: 1
Identification and general information on the bus module CPX-E-EP.
Service Code 5
d
Parameter 0 emulates a power cycle
Parameter 1 resets the device to the factory settings and then emulates a power cycle
Attribute no.
Access
1
Get
2
Get
3
Get
4
Get
5
Get
6
Get
7
Get
8
Get
14
Get/Set
15
Get/Set
(NV)
16
Get/Set
(NV)
17
Get/Set
(NV)
100
Get
101
Get
Tab. 3.16
26
: Reset
Description
VendorID: 1A
h
Device type: 0C
h
Product code: 36D8
h
Revision (major/minor)
Status
Bit 0
Owned
Bit 1
Reserved, shall be 0
Bit 2
Configured
Bit 3
Reserved, shall be 0
Bit 4 ... 7
Extended device status
Bit 8
Minor recoverable fault
Bit 9
Minor unrecoverable fault
Bit 10
Major recoverable fault
Bit 11
Major unrecoverable fault
Bit 12 ... 15
Reserved, shall be 0
Serial number
Product name (CPX-E-EP Remote I/O)
State
0 = Nonexistent
1 = Device self testing
2 = Standby
3 = Operational
4 = Major recoverable fault
5 = Major unrecoverable fault
255 = Default value
Semaphore
User assigned name
User assigned description
User assigned location
Operating mode
External module identifiers
Type
UINT
UINT
UINT
STRUCT
WORD
UDINT
SHORT_STRING
USINT
STRUCT
STRING
STRING
STRING
BOOL
ARRAY
Festo – CPX-E-EP-EN – 2017-07 – English