Festo CPX-E-EP Manual page 28

System cpx-e, bus module, protocol, ethernet/ip, modbus tcp, industrial ethernet 2-port
Table of Contents

Advertisement

3
Parameterisation
Attribute no.
Access
10
Get/Set
11
Get/Set
12
Get/Set
13
Get/Set
1) Indicates whether the current expansion of the system CPX-E corresponds to the saved expansion.
2) SCS = Short circuit/overload in sensor supply
3) SCO = Short circuit/overload at the outputs
4) SCV = Short circuit at valves
5) Presetting
Tab. 3.17
Status and Diagnostics Object
Object class: 133
d
Instances: 1
Mapping of status bits and of I/O diagnostic interface.
Attribute no.
Access
1
Get
2
Get
3
Get
4
Get
5
Get/Set
6
Get
1) Source of error = Bit 0 ... 3; type of error = Bit 4 ... 7
Tab. 3.18
28
Description
Fail safe mode (bit 0, 1)
5)
0 = Reset all outputs
1 = Retain signal status
2 = Assume Fail safe mode
Force mode (bit 2, 3)
0 = Force mode blocked
1 = Force mode enabled
System Idle mode (bit 4, 5)
5)
0 = Reset all outputs
1 = Retain signal status
2 = Assume Idle mode
System start (bit 6)
0 = System start with standard parameters
(factory setting) and current expansion; external
parameterisation possible (presetting)
1 = System start with saved parameters and
saved expansion; parameters and expansion are
saved to retentive memory; external
parameterisation is blocked; the "M" LED on the
bus module is lit up
Description
1)
Status bits
Bit 0
Valve
Bit 1
Outlet
Bit 2
Input
Bit 3
Analogue/technology module
Bit 4
Undervoltage
Bit 5
Short circuit/overload
Bit 6
Wire break
Bit 7
Other error
Number of the first module in which an error has
occurred
Diagnostic status
Error number
Address of I/O diagnostic interface
16 output bits (order data)
Data for I/O diagnostic interface
16 input bits (reply data)
Type
Function number
USINT
4402 (bit 0, 1)
USINT
4402 (bit 2, 3)
USINT
4402 (bit 4, 5)
USINT
4402 (bit 6)
Type
Function number
USINT
1936
USINT
1937
USINT
UINT
1938
WORD
WORD
Festo – CPX-E-EP-EN – 2017-07 – English