Festo CPX-E-EP Manual page 24

System cpx-e, bus module, protocol, ethernet/ip, modbus tcp, industrial ethernet 2-port
Table of Contents

Advertisement

3
Parameterisation
Instance 100 (Output data)
Within instance 100, all outputs of the system CPX-E are transmitted cyclically over the network.
The following sequence applies during transmission:
1. I/O diagnostic interface or status bits, if activated (16-bit oriented)
2. Object instances of the analogue channels (16-bit oriented)
3. Instances of the technology modules (16- or 8-bit oriented)
4. Object instances of the digital outputs (8-bit oriented)
Instance 100 (output) has the following member list:
1)
Object
Instances
103
1 ... 48
105
107
133
1
1) Instances = Module number + 1
Tab. 3.9
Instance 102 (Configuration data)
Instance 102 has the following member list:
Object
Quantity
Entry in member list
199
1
Configuration array data
Tab. 3.10
The I/O objects 102 ... 107 also have the following attributes:
Attribute
Entries
100
Number of data of the module in BYTE or WORD
101
Data type:
D1
: BYTE
h
D2
: WORD
h
102
All data values
Tab. 3.11
24
Attributes (channel) Entry in member list
1 ... 64
Digital data
1 ... 32
Analogue channel data
1 ... 64/65 ... 96
Technology module
0/1
I/O diagnostic interface data, if activated
Type
BOOL
WORD
BYTE/WORD
WORD
Type
ARRAY
Type
BYTE
BYTE
ARRAY
Festo – CPX-E-EP-EN – 2017-07 – English

Advertisement

Table of Contents
loading