38 Start-up

Speed reference

For using the fieldbus to provide input speed references to the
drive, configure the following drive parameters and set the fieldbus
controller supplied reference word(s) in the appropriate location:
Drive parameter
19.11 Ext1/Ext2
selection
22.11 Ext1 speed
ref1
22.18 Ext2 speed
ref1
46.01 Speed
scaling
50.04 FBA A ref1
type/50.05 FBA A
ref2 type
1)
As example

Miscellaneous drive control

To use the fieldbus for different drive control functions, configure
the following drive parameters and set the fieldbus controller
supplied command(s) in the appropriate location:
Drive parameter
20.40 Run permissive Fieldbus
20.01 Ext1
commands/
20.06 Ext2
commands
Value
Description
2 = FBA A
Reference set
MCW bit
selection by fieldbus
1)
3 =FBA ref1
Speed reference
source 1
1)
5 =FBA ref2
Speed reference
source 2
1)
1500 rpm
16-bit scaling of
speed-related
parameters
0 = Speed or
References (1 or 2)
frequency
type for scaling
4 = Speed
defined in parameter
46.02 Frequency
scaling
Value
Description
Run permission by
adapter
fieldbus
Fieldbus A
Fault reset by fieldbus BV14
BACnet
access point
BV13
AV16
AV17
AV16/AV17
AV16/AV17
BACnet
access point
BV12