56 Communication protocol

BI object

Object
Default
ID
object name
BI0
RO1-Monitor
BI1
RO2-Monitor
BI2
RO3-Monitor
BI3
RO4-Monitor
BI4
RO5-Monitor
BI5
DO1-Monitor
BI6
DI1-Monitor
BI7
DI2-Monitor
BI8
DI3-Monitor
BI9
DI4-Monitor
BI10
DI5-Monitor
BI11
DI6-Monitor
Description
Status of Relay Output 1
Status of Relay Output 2
Status of Relay Output 3
Status of Relay Output 4
Status of Relay Output 5
Status of Digital Output 1
Status of Digital Input 1
Status of Digital Input 2
Status of Digital Input 3
Status of Digital Input 4
Status of Digital Input 5
Status of Digital Input 6
Default
Present
active/
value
Inactive
access
text
type
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF
ON /
R
OFF

Advertisement