58 Communication protocol
Object
Default
ID
object
name
BV8
At-Setpoint-
Monitor
BV9
Enabled-
Monitor
BV10
RUN-STOP-
Command
BV11
Direction-
Command
BV12
Run-
Permissive-
Command
BV13
EXT1-EXT2-
Command
BV14
Fault-Reset-
Command
BV18
Control-
Override-
Command
BV19
Control-
Override-
Monitor
Description
Actual at setpoint status
Actual run enabled
status
Command to start drive
Command to rotational
direction
Command to Run
Permissive command
Command to External 1
or External 2
Command to fault reset
Command the drive into
BACnet Control
Override. In this mode
BACnet acquires drive
control from its normal
source.
Note: The HAND mode
of the panel has priority
over BACnet Control
Override.
Indicates if drive is
placed in BACnet Control
Override by commanding
BV18. In this mode
BACnet acquires drive
control from its normal
source. Note that HAND
mode of the panel has
priority over BACnet
Control Override.
Default
Present
active/
value
Inactive
access
text
type
YES / NO
R
ENABLE /
R
DISABLE
RUN /
C
STOP
REVERSE /
C
FORWARD
ENABLE /
C
DISABLE
EXT2 /
C
EXT1
RESET /
W
NO
ON / OFF
C
ON / OFF
R

Advertisement