Data point connections
The BACnet access points in the above drive parameter
connections are linked to the following data points:
BACnet
access point
AO0
AO1
PID control
For PID control through fieldbus, configure the following drive
parameters and set the fieldbus controller supplied PID value(s) in
the appropriate location:
Drive parameter
40.08 Set 1
feedback 1 source
40.09 Set 1
feedback 2 source
40.16 Set 1
setpoint 1 source
40.17 Set 1
setpoint 2 source
Drive parameter
13.91 AO1 data
storage
13.92 AO2 data
storage
Value
Feedback
storage
Feedback
storage
Setpoint data
storage
Setpoint data
storage
Description
Storage parameter for AO1
Storage parameter for AO2
Description
Feedback 1 source
data storage
Feedback 2 source
data storage
Setpoint 1 source
data storage
Setpoint 2 source
data storage
Start-up 41
BACnet
access point
AV43
AV43
AV42
AV42