46 Start-up
Starting up fieldbus communication for ACH580
drives
Follow these steps to setup fieldbus communication in ACH580
drives. For example of appropriate values, see
examples
(page 47).
1. Power up the drive.
2. Enable communication between the adapter module and the
drive with parameter 50.01 FBA A enable.
3. Configure network settings with parameters 51.03...51.13.
4. Define the device object instance value with parameters 51.14
Device obj ID lo and 51.15 Device obj ID hi.
Note: The object instance value should be unique and in the
range 1...4194303.
5. Define communication loss function to monitor the
communication between fieldbus master and adapter module
and between adapter module and drive:
With parameters 51.20 and 51.21, set the timeout time and
timeout mode.
With parameter 50.03 FBA A comm loss t out, define the
communication break reaction time.
With parameter 50.02 FBA A comm loss func, select how
the drive reacts to a fieldbus communication break.
6. With parameter 96.07 Parameter save manually, save the
valid parameter values to permanent memory.
7. With parameter 51.27 FBA A par refresh, validate the settings
made in parameter group 51.
8. Set the relevant drive control parameters to control the drive
according to the application.
Parameter setting