BO object

Object
Default object
ID
name
BO0
RO1-Command Output state of Relay 1
BO1
RO2-Command Output state of Relay 2
BO2
RO3-Command Output state of Relay 3
BO3
RO4-Command Output state of Relay 4
BO4
RO5-Command Output state of Relay 5
BO5
DO1-Command Output state of Digital

BV object

Object
Default
ID
object
name
BV0
RUN-STOP-
Monitor
BV1
Direction-
Monitor
BV2
OK-FAULT-
Monitor
BV3
EXT1-EXT2-
Monitor
BV4
HAND-
AUTO-
Monitor
BV5
Warning-
Monitor
BV7
Ready-
Monitor
Description
Output 1
Description
Run status of drive
Rotational direction of
the motor
Actual fault status of
drive
Actual control source
Actual operating mode
Actual warning status
Actual ready status
Communication protocol 57
Default
active/
Inactive
text
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
ON / OFF
Default
active/
Inactive
text
RUN /
STOP
REVERSE /
FORWARD
FAULT / OK R
EXT2 /
EXT1
HAND /
AUTO
WARNING /
OK
READY /
NOT-
READY