ABB FBIP-21 BACnet/IP User Manual page 63

Table of Contents

Advertisement

Name
Color
Red
Flashing
orange,
alternating
with the
HOST
flashing
orange
Flashing
red/green
NET
Off
Flashing
green
Flashing
orange
Function
• Ethernet interface is disabled.
• Duplicate Address Detection may have
detected a duplicate address. Check the
IP configuration and either initiate a
Fieldbus Adapter parameter refresh or
cycle power to the drive.
or
• Drive is not supported by FBIP-21.
Internal file system error. The error may be
cleared by cycling drive power. If the error
persists, contact your local ABB
representative.
Device is in boot mode, ready for firmware
update (HOST led is Off).
BACnet link is down.
BACnet link is up at 100 Mbps.
Flashing indicates activity on interface.
BACnet link is up at 10 Mbps.
Flashing indicates activity on interface.
Diagnostics 63