32 Start-up
No.
Name/Value
10
GW address 1
0...255
...
...
13
GW address 4
0...255
14
Device obj ID lo Defines the device object ID for
0...9999
15
Device obj ID hi Defines the device object ID for
0...419
16
Max APDU
retries
0...10
17
APDU timeout
6...60 s
Description
Defines the four octets of the gateway
address.
IP gateways connect individual
physical IP subnets into a unified IP
network.
An IP node on one subnet
communicates with an IP node on
another subnet by sending data to the
IP gateway for forwarding. Parameters
10...13
define the four octets of the
gateway address.
GW address
...
See parameter
10 GW address
GW address
BACnet devices.
The Device Object ID needs to be
unique across all BACnet devices in
the building network.
Valid values are 0...4194303.
For values 0...9999, this parameter
sets the values directly. For values
greater than 9999, the ID is calculated
with this formula:
Device ID = (10000 * par. 15) + par. 14.
Device ID
BACnet devices.
Device ID
Defines the number of retries to send
when no response is seen to
confirmed requests.
Number of retries.
Defines the time a client waits for
response from a BACnet device.
Waiting time.
Default
0
...
1.
0
0
0
3
6 s