Keypad Display; Control Specifications; Differential Analog Input - Baldor 22H series Installation & Operating Manual

Line regen ac flux vector control vector drive
Table of Contents

Advertisement

Section 1
General Information

Keypad Display:

Display
Keys
Functions
LED Indicators
Remote Mount

Control Specifications:

Control Method
Velocity Loop Bandwidth
Current Loop Bandwidth
Maximum Output Frequency
Standard Frequency Version
Quiet Frequency Version
Selectable Operating Modes

Differential Analog Input:

Common Mode Rejection
Full Scale Range
Resolution
Update rate
7-2 Specifications, Ratings & Dimensions
Backlit LCD Alphanumeric
2 Lines x 16 Characters
12 key membrane with tactile response
Output status monitoring
Digital speed control
Parameter setting and display
Diagnostic and Fault log display
Motor run and jog
Local/Remote toggle
Forward run command
Reverse run command
Stop command
Jog active
100 feet (30.3m) max from control
PWM
Adjustable to 180 Hz
Adjustable to 1200 Hz
1000 Hz
Full rating 1-2.5 KHz PWM frequency,
Adjustable to 5 KHz with linear derating (between 2.5 - 5KHz)
by 10% at 5 KHz
Full rating 1-8 KHz PWM frequency,
Adjustable to 16 KHz with linear derating (between 8 - 16KHz)
by 30% at 16 KHz
Keypad
Standard 3 Wire Control
Two Wire Control with 15 Preset Speeds
Fan Pump, 2 Wire Control
Fan Pump, 3 Wire Control
Bipolar Speed/Torque Control
Serial
Process
40 db
5VDC, 10VDC, 4-20 mA
9 bits + sign
500 sec
MN722