Section 1
General Information

Control Circuit Connections

Converting Control Board Connections

Optional
Customer
Supplied
Relays
Using Internal Supply
(Sinking the Relay Current)
3-24 Receiving & Installation
There are two control boards in a Series 22H Vector Control. The Converting Control
Board is used to rectify and process the incoming power. The Power Output Control
Board provides the inverting and power output functions. The keypad is normally
connected to the Power Output Control Board. Each converter board has its own J1
terminal strip. The Power Output Control Board provides the user interface for most
external connections.
All necessary connections for the Converting Control Board have been made at the
factory prior to shipment.
The jumper between J1-8 and J1-17 provides the enable signal to allow converter
operation. The jumper between J1-39 and J1-40 provides +24VDC from the internal
supply to allow the opto isolated input at J1-8 to operate. These jumpers should remain
installed at all times.
Sometimes it is necessary to troubleshoot the converter section using the isolated opto
outputs. Figure 3-10 shows how to connect external relays to the board to "Sink" or
"Source" the relay current.
The function of each opto output is as follows: (these functions cannot be changed)
J1-19
Ready
J1-20
At Voltage
J1-21
Fault
J1-22
Overtemperature Warning
Figure 3-10 Converting Control Board Opto Output Wiring
+24VDC
24COM
17
39
18
40
19
41
20
42
21
43
22
44
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
+24VDC
24COM
17
39
18
40
19
41
20
42
21
43
22
44
Using Internal Supply
(Sourcing the Relay Current)
Optional
Customer
Supplied
Relays