Table 4-4
Block Title
Parameter
KEYPAD SETUP
Keypad Stop Key
Keypad Stop Mode
Keypad Run FWD
Keypad Run REV
Keypad Jog FWD
Keypad Jog REV
INPUT
Operating Mode
Command Select
ANA CMD Inverse
ANA CMD Offset
ANA 2 Deadband
ANA 1 CUR Limit
MN722
Power Output Control Board
Description
Stop Key -
Stop Mode - Selects if the Stop command causes the motor to "COAST" to a stop or
Run FWD -
Run REV -
Jog FWD -
Jog REV -
Eight "Operating Modes" are available. Choices are: Keypad, Standard Run, 15SPD,
Fan Pump 2 Wire, Fan Pump 3 Wire, Serial, Bipolar, and Process. External
connections to the control are made at the J1 terminal strip (wiring diagrams are
shown in Section 3 "Control Circuit Connections").
Selects the external speed reference to be used. The easiest method of speed control is
to select POTENTIOMETER and connect a 5K
or 4-20mA input command can be applied to J1-4 and J1-5.
If long distance is required between the external speed control and the control, the 4-20mA
selections at J1-4 and J1-5 should be considered. Current loop allows long cable lengths
without attenuation of the command signal.
10 VOLT W/TORQ FF - when a differential command is present at J1-4 and 5, allows addi-
tional 5V torque feedforward input at J1-1, 2 and 3 to set a predetermined amount of
torque inside the rate loop with high gain settings.
EXB PULSE FOL - selects optional Master Pulse Reference/Isolated Pulse Follower ex-
pansion board if installed.
5VOLT EXB - selects optional High Resolution I/O expansion board if installed.
10VOLT EXB - selects optional High Resolution I/O expansion board if installed.
3-15 PSI EXB selects optional 3-15 PSI expansion board if installed.
Tachometer EXB- selects optional DC Tachometer expansion board if installed.
Serial -selects optional Serial Communications expansion board if installed.
None - Used in Process Control mode, two input configuration with no Feedforward input.
Note: When using the 4-20mA input, the JP1 jumper on the main control board
"OFF" will cause a low input voltage (e.g. 0VDC) to be a low motor speed command and
a maximum input voltage (e.g. 10VDC) to be a maximum motor speed command.
"ON" will cause a low input voltage (e.g. 0VDC) to be a maximum motor speed command
and a maximum input voltage (e.g. 10VDC) to be a low motor speed command.
Provides an offset to the Analog Input to minimize signal drift. For example, if the
minimum speed signal is 1VDC (instead of 0VDC) the ANA CMD Offset can be set to
-10% so the minimum voltage input is seen by control as 0VDC.
Allows a defined range of voltage to be a deadband. A command signal within this
range will not affect the control output. The deadband value is the voltage above and
below the zero command signal level.
Allows the 5V input at J1-2 (referenced to J1-1) to be used for reduction of the
programmed current limit parameter for torque trimming during operation.
Level 1 Parameter Definitions
Allows keypad "STOP" key to initiate motor stop during remote or serial
operation (if Stop key is set to Remote ON). If active, pressing "STOP"
automatically selects Local mode and initiates the stop command.
"REGEN" to a stop. In COAST, the motor is turned off and allowed to
coast to a stop. In REGEN, the voltage and frequency to the motor is
reduced at a rate set by "Decel Time".
d
d t
t
t b "D
ON makes the keypad "FWD" key active in Local mode.
ON makes the keypad "REV" key active in Local mode.
ON makes the keypad "FWD" key active in Local Jog mode.
ON makes the keypad "REV" key active in Local Jog mode.
must be moved to pins 2 and 3.
- Continued
g
q
y
l Ti
"
pot to J1-1, J1-2, and J1-3.
Programming & Operation 4-15
5, 10VDC