Figure 3-7 Encoder Connections
No Connection
Terminal Tightening Torque = 7 Lb-in (0.8 Nm).
Encoder Cable Connection
Encoder cable must be separated by at least 3" (76mm) from parallel runs of power
wires. Encoder cables that cross power wires must cross at a 90 angle only. Encoder
wires must be #22 AWG (0.34mm
have an overall shield.
Note: Be careful not to pinch the wires' insulation in J1 terminals as proper electrical
connection may not be made.
1.
Feed the control end of the cable through one of the "Knock-out" holes in the
control case so connections can be made inside the control.
2.
Differential Connections
Connect the cable braided shield to J1-30 at control end only.
For Baldor standard vector encoder, connect the cable ends as follows:
(See Figure 3-7.)
Encoder End
A
H
B
J
C
K
D
F
E
Note: Encoders other than a Baldor Standard Vector Encoder may require different
connections. Refer to information provided by the manufacturer and connect
the proper signals to the "Control End" J1 connections.
3.
Single Ended Connections
Differential inputs are recommended for best noise immunity. If only single
ended encoder signals are available, connect them to A, B, and INDEX (C)
(J1-23, J1-25 and J1-27 respectively).
2
) minimum, 200 feet (60m) maximum length and must
Control End
J1-23 (A)
J1-24 (A)
J1-25 (B)
J1–26 (B)
J1–27 Index(C)
J1–28 Index(C)
J1–29 (+5VDC)
J1–30 (Common)
No Connection
H
A
B
G
K
J
C
F
E
D
Receiving & Installation 3-21