Encoder Installation

3-20 Receiving & Installation
Electrical isolation of the encoder shaft and housing from the motor is required. Electrical
isolation helps prevent capacitive coupling of motor noise that will corrupt the encoder
signals. See electrical noise considerations in Section 7 of this manual.
Cable Preparation
Encoder wiring must be shielded twisted pairs, #22 AWG (0.34mm
200 (60m) maximum, with an insulated overall shield.
Control End (See Figure 3-6.)
1.
Strip the outside jacket approximately 0.375 (9.5mm) from the end.
2.
Solder a #22 AWG (0.34mm
3.
Connect all shields to J1-30. To do this, solder a "Drain Wire" from each shield
to the wire soldered to the braided shield in step 2.
4.
Insulate or tape off ungrounded end of shields to prevent contact with other
conductors or ground.
Encoder End
1.
Strip the outside jacket approximately 0.375 (9.5mm) from the end.
2.
Identify each of the four twisted pair and label or use the color codes shown in
Figure 3-7 for the optional Baldor Encoder Cable.
3.
Insulate or tape off ungrounded end of shields and unused conductors to
prevent contact with other conductors or ground.
CAUTION: Do not connect any shields to the encoder case or motor frame.
The encoder +5VDC supply at J1-29 is referenced to circuit board
common. Do not connect any shields to ground or another power
supply or damage to the control may result.
Figure 3-6 Encoder Cables
2
) wire to the braided shield.
No. 9891
2
) minimum size,
MN722