2. Diagnosis
2.3

Diagnostics via fieldbus

2.3.1 Diagnostics via SDO
2.3.2 The Emergency Message
Byte 0
Byte 1
Error code
CANopen standard
Tab. 2/6:
Composition of the Emergency Message Object
Festo P.BE-CTEU-CO-OP+MAINT-EN en 1101NH
The master controller can query diagnostic information via
SDO access on the bus node. The corresponding SDOs can be
found in the object directory in section A.2.
If an error occurs the bus node can send an emergency
message with a defined structure (see Tab. 2/6) when the
"diagnostics" DIL switch is activated (see section 2.1). The
following sections describe the components of the emergency
message and the error causes (see Tab. 2/9).
Note
As a prerequisite Node guarding or Heartbeat must be
activated on the master controller.
Byte 2
Byte 3
Error Re-
Device 1
gister
Dia-
gnostics
byte 1
Obj. 1001
Obj. 1002
Manufacturer status register
Manufacturer specific error field
Byte 4
Byte 5
Device 2
Dia-
Dia-
gnostics
gnostics
byte 2
byte 1
Byte 6
Byte 7
Reserved
Dia-
gnostics
byte 2
2-9