Orientation; Inlet And Outlet Runs (Clamp-On Version) - Endress+Hauser Proline Prosonic Flow 90 Operating Instructions Manual

Ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow 90:
Table of Contents

Advertisement

Proline Prosonic Flow 90
Endress+Hauser
3.2.3

Orientation

Vertical orientation
Recommended orientation with upward direction of flow (View A). Entrained solids sink down.
Gases rise away from the measuring sensor when fluid is not flowing. The piping can be completely
drained and protected against build-up.
Horizontal orientation
In the recommended installation range in a horizontal installation position (View B), gas and air
accumulation at the pipe cover and problematic build-ups at the bottom of the pipe have a minor
influence on the measurement.
A
Fig. 7:
Installation position (A = vertical, B = horizontal, C = recommended installation range max. 120°)
3.2.4

Inlet and outlet runs (clamp-on version)

If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc. If several
flow obstructions are installed, the longest inlet or outlet run must be considered. Compliance with
the following requirements for the inlet and outlet runs is recommended to ensure measuring accu-
racy.
1
2
3
Fig. 8:
Inlet and outlet runs (clamp-on version)
1 = Valve; 2 = Pump; 3 = Two pipe bends in different directions
C
B
³ 15 x DN
³ 5 x DN
³ 40 x DN
³ 20 x DN
³ 40 x DN
3 Installation
C
A0001105
A0001106
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents