Universal / Common Practice Hart Commands - Endress+Hauser Proline Prosonic Flow 90 Operating Instructions Manual

Ultrasonic flow measuring system
Hide thumbs Also See for Proline Prosonic Flow 90:
Table of Contents

Advertisement

5 Operation
Command No.
HART command / Access type
Universal Commands
0
Read unique device identifier
Access type = read
1
Read primary process variable
Access type = read
2
Read the primary process variable
as current in mA and percentage
of the set measuring range
Access type = read
52
5.5.4

Universal / common practice HART commands

The following table contains all the universal and common practice commands supported by
Prosonic Flow 90.
Command data
(numeric data in decimal form)
none
none
none
Proline Prosonic Flow 90
Response data
(numeric data in decimal form)
Device identification provides information on the
device and manufacturer and cannot be changed.
The response consists of a 12 byte device ID:
– Byte 0: fixed value 254
– Byte 1: Manufacturer ID, 17 = E+H
– Byte 2: Device type ID, 88 = Prosonic Flow 90
– Byte 3: Number of preambles
– Byte 4: Rev. no. universal commands
– Byte 5: Rev. no. device-specific commands
– Byte 6: Software revision
– Byte 7: Hardware revision
– Byte 8: Additional device information
– Byte 9
11: Device identification
– Byte 0: HART unit code of the primary process
variable
– Byte 1
4: Primary process variable
Factory setting:
Primary process variable = Volume flow
!
Note!
• You can set or change the assignment of device
variables to process variables using Command 51.
• Manufacturer-specific units are represented using
the HART unit code "240".
– Byte 0
3: Present current of the primary process
variable in mA
– Byte 4
7: Percentage of the set measuring range
Factory setting:
Primary process variable = Volume flow
!
Note!
You can set or change the assignment of device
variables to process variables using Command 51.