7.2.1.2 Setting Protect Parameters

Procedure
Step 1 Choose Function Menu > Settings > Protect Parameters to access the settings screen.
Figure 7-3 Protect parameters (advanced user)
----End
Parameter List
No.
Parameter
1
Insulation
resistance
protection

7.2.1.3 Setting Feature Parameters

Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings screen.
Issue 02 (2018-10-15)
Description
To ensure device safety,
the SUN2000 detects the
insulation resistance
between the input side and
the ground when it starts a
self-check. If the detected
value is less than the preset
value, the SUN2000 does
not export power to the
power grid.
Copyright © Huawei Technologies Co., Ltd.
Unit
Default Value
MΩ
0.037
7 Man-Machine Interactions
Value Range
[0.033, 1.500]