Huawei SUN2000-60KTL-M0 User Manual page 103

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
Alarm
Alarm
Alarm
ID
Name
Severity
Current
2061
Abnorm
Major
al
Groundi
ng
2062
Low
Major
Insulatio
n
Resistan
ce
2063
Cabinet
Major
Overtem
perature
2064
Device
Major
Fault
Upgrade
2065
Minor
Failed
Issue 02 (2018-10-15)
Cause
SUN2000 is operating.
1. The PE cable for the SUN2000 is
not connected.
2. The SUN2000 output side does not
connect to an isolation transformer
when the PV string output is
grounded.
1. The PV string is short-circuited to
PE.
2. The PV string has been in a moist
environment for a long time and the
power cable is not well insulated to
ground.
1. The SUN2000 is installed in a place
with poor ventilation.
2. The ambient temperature exceeds
the upper threshold.
3. The SUN2000 is not working
properly.
An unrecoverable fault occurs on a
circuit inside the SUN2000.
The upgrade ends abnormally.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Measures
temporarily. The SUN2000
automatically recovers after the
fault is rectified.
2. If the alarm occurs frequently
or persists, check that the
impedance between the PV
string and ground is not below
the lower threshold.
1. Check that the PE cable for the
SUN2000 is connected
properly.
2. If the PV string output is
grounded, check that the
SUN2000 output side connects
to an isolation transformer.
1. Check the impedance between
the PV string and the PE cable.
If a short circuit occurs, rectify
the fault.
2. Check that the PE cable for the
SUN2000 is correctly
connected.
3. If you are sure that the
impedance is less than the
default value in a cloudy or
rainy environment, reset
Insulation resistance
protection.
1. Check the ventilation and
ambient temperature at the
SUN2000 installation position.
If the ventilation is poor or the
ambient temperature exceeds
the upper threshold, improve
the ventilation and heat
dissipation.
2. If the ventilation and ambient
temperature both meet
requirements, contact Huawei
technical support.
Turn off the AC output switch and
DC input switch, and then turn
them on after 15 minutes. If the
fault persists, contact Huawei
technical support.
1. Perform an upgrade again.
2. If the upgrade fails several
times, contact your dealer.
97

Hide quick links:

Advertisement

Table of Contents
loading