Huawei SUN2000-60KTL-M0 User Manual page 72

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
Figure 6-8 Quick Settings screen (advanced user)
Issue 02 (2018-10-15)
Set the grid code that applies to the country or region where the PV plant is located and the
SUN2000 model.
Set user parameters based on the current date and time.
Set Baud rate, Protocol, and Address based on site requirements. Baud rate can be set to 4800,
9600, or 19200. Protocol can be set to MODBUS RTU, and Address can be set to any value in the
range of 1 to 247.
When multiple SUN2000s communicate with the SmartLogger over RS485, the RS485 addresses
for all the SUN2000s on each RS485 route must be within the address range set on the SmartLogger
and cannot be duplicate. Otherwise, the communication will fail. In addition, the baud rates of all the
SUN2000s on each RS485 route must be consistent with the SmartLogger baud rate.
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning
66