Setting Feature Parameters - Huawei SUN2000-60KTL-M0 User Manual

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
No.
Parameter
2
Phase angle offset
protection
3
10 minute OV protection
4
10 minute OV protection
time
5
Level-1 OV protection
6
Level-1 OV protection
time
7
Level-1 UV protection
8
Level-1 UV protection
time
9
Level-1 OF protection
10
Level-1 OF protection time
11
Level-1 UF protection
12
Level-1 UF protection time

7.2.2.3 Setting Feature Parameters

Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings screen.
Issue 02 (2018-10-15)
Description
The standards of certain countries
and regions require that the
SUN2000 needs to be protected
when the three-phase angle offset
of the power grid exceeds a
certain value.
Specifies the 10-minute
overvoltage protection threshold.
Specifies the 10-minute
overvoltage protection duration.
Specifies the level-1 overvoltage
protection threshold.
Specifies the level-1 overvoltage
protection duration.
Specifies the level-1 undervoltage
protection threshold.
Specifies the level-1 undervoltage
protection duration.
Specifies the level-1
overfrequency protection
threshold.
Specifies the level-1
overfrequency protection
duration.
Specifies the level-1
underfrequency protection
threshold.
Specifies the level-1
underfrequency protection
duration.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Unit
Value Range
N/A
Disable
Enable
V
[1 x Vn, 1.4 x Vn]
ms
[50, 7200000]
V
[1 x Vn, 1.4 x Vn]
ms
[50, 7200000]
V
[0.15 x Vn, 1 x Vn]
ms
[50, 7200000]
Hz
[1 x Fn, 1.15 x Fn]
ms
[50, 7200000]
Hz
[0.85 x Fn, 1 x Fn]
ms
[50, 7200000]
85