Huawei SUN2000-60KTL-M0 User Manual page 96

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
No.
Parameter
8
Power factor
Reactive
9
power
compensation
(Q/S)
10
Reactive
power
compensation
at night (Q/S)
11
Trigger
frequency of
over
frequency
derating
12
Quit
frequency of
over
frequency
derating
Recovery
13
gradient of
over
frequency
derating
14
Overfrequenc
y derating
Issue 02 (2018-10-15)
Description
Adjusts the SUN2000
power factor.
Adjusts the SUN2000
output reactive power.
If Reactive power output
at night is set to Enable,
no PV input exists, and no
remote scheduling
instruction is delivered,
the SUN2000 responds to
this command.
The standards of certain
countries and regions
require that the output
active power of the
SUN2000 be derated
when the grid frequency
exceeds a certain value.
Specifies the frequency
threshold for exiting
overfrequency derating.
Specifies the power
recovery gradient for
overfrequency derating.
If this parameter is
enabled, the active power
of the inverter will be
derated according to a
certain slope when the
grid frequency exceeds
the value that triggers
overfrequency derating.
Copyright © Huawei Technologies Co., Ltd.
Unit
Value Range
N/A
(–1.000,
–0.800]U[0.800,
1.000]
N/A
(-1, 1]
N/A
(-1, 1]
Hz
When the output
frequency is 50
Hz, the value
range is
45.00–55.00 Hz.
When the output
frequency is 60
Hz, the value
range is
55.00–65.00 Hz.
Hz
When the output
frequency is 50
Hz, the value
range is
45.00–55.00 Hz.
When the output
frequency is 60
Hz, the value
range is
55.00–65.00 Hz.
%/min
[5, 20]
N/A
Disable
Enable
7 Man-Machine Interactions
Remarks
N/A
N/A
N/A
Fn represents the
rated frequency.
N/A
N/A
90

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents