Huawei SUN2000-60KTL-M0 User Manual page 82

Three-phase grid-tied pv string inverter
Hide thumbs Also See for SUN2000-60KTL-M0:
Table of Contents

Advertisement

SUN2000-60KTL-M0
User Manual (Europe Edition)
No.
Parameter
Description
should comply with
the standard. If an AC
switch with a residual
current detection
function is installed
outside the SUN2000,
this function should
be enabled to reduce
the residual current
generated during
SUN2000 running,
thereby preventing the
AC switch from
misoperations.
4
Reactive
In some specific
power
application scenarios,
output at
a power grid company
night
requires that the
SUN2000 can
perform reactive
power compensation
at night to ensure that
the power factor of
the local power grid
meets requirements.
PID
5
protection
at night
Issue 02 (2018-10-15)
Unit
N/A
When PID
N/A
protection at
night is set to
Enable, the
SUN2000 will
shut down
automatically if it
detects
abnormality in
PID voltage
compensation
during the reactive
power
compensation at
night.
When PID
protection at
night is set to
Disable, the
SUN2000 will
operate in grid-tied
mode if it detects
abnormality in
PID voltage
compensation
Copyright © Huawei Technologies Co., Ltd.
Default
Value Range
Value
Disable
Disable
Enable
Enable
Disable
Enable
7 Man-Machine Interactions
Remarks
This parameter is
configurable only
when Isolation is set
to Input
ungrounded, with a
transformer.
N/A
76